ATS-TCP-1000
Tubed Cold Plates
  • Cost effective thermal management solution for component cooling where the heat load is low to moderate
  • Compatible with industry accepted coolants
  • The cold plate base the copper tubes press into is made of aluminum 6063
  • Copper tubed cold plates are attached to the base plate with a thin film of high thermal conductivity epoxy for secure tube attachment.
  • Stainless steel tubed cold plates are SS 304/316 and feature tubing secured between two plates
  • Supplied with secure, 3/8“ push-to-connect tube fittings for a tight connection between the cold plate and inlet and outlet tubing. Tube outer diameter is 3/8“ (9.525 mm).
  • Maximum pressure: 200 psi
  • Plastic tubing connecting to our Cold Plate fitting has to be at least 90 durometer Shore A scale
Product Details
Part Number Lifecycle
Status
Plate Dimension (mm) Overall
Length
(mm)
# No
of Tube
Pass
Tube
Material
Flow Rate
LPM(GPM) 1.9(0.5)
Flow Rate
LPM(GPM) 3.7(1.0)
Flow Rate
LPM(GPM) 5.7(1.5)
Flow Rate
LPM(GPM) 7.6(2.0)
Length Width Height R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
R
(°C/W)
dP
kPA (psi)
ATS-TCP-1000 ACTIVE 57.0 57.0 15.0 133 2 Copper 0.088 1.03 (0.15) 0.075 3.24 (0.47) 0.067 6.55 (0.95) 0.063 11.1 (1.61)
Thermal Performance
Schematic Image Thermal Resistance
Flow Rate
LPM(GPM)
R
(°C/W)
dP
kPA (psi)

*Image above is for illustration purpose only.
1.9(0.5) 0.088 1.03 (0.15)
3.7(1.0) 0.075 3.24 (0.47)
5.7(1.5) 0.067 6.55 (0.95)
7.6(2.0) 0.063 11.1 (1.61)
ATS-TCP-1000    (Data Sheet)
download data sheet
ATS-TCP-1000
Mechanical Drawing - FUSED MODEL (used for Form and Fit use)
download fused Model for Form and Fit use
RoHS & REACH Certificate download data sheet
Complete Your Liquid Loop with ATS

ATS has the products needed to design a complete liquid cooling loop : iCDMs (Industrial Cooling Distribution Modules), Tubed and High Performance Cold Plates to transfer and remove the heat from the source; Heat Exchangers to transfer heat from the liquid to the air with or without a fan; Chillers to circulate and condition the fluid in the system, Compact Refrigeration Modules for very high capacity cooling. In addition , ATS offers Flow Meters to measure the volumetric flow rate of the fluid in the system and Leak Detectors to notify users of any leaks in the system.